Article No.
|
6XV1 840-2AH10
|
6XV1 841-2A
|
6XV1 870-2B
|
6XV1 841-2B
|
Product-type designation
|
IE FC TP Standard Cable GP 2 x 2 (Type A)
|
IE FC TP Robust Standard Cable GP 2 x 2 (Type A)
|
IE FC TP Flexible Cable GP 2 x 2 (Type B)
|
IE FC TP Robust Flexible Cable GP 2 x 2 (Type B)
|
Product descrtption
|
|
|
|
|
Acceptability for application
|
Standard cable with rigid cores for fast installation
|
Standard cable with rigid cores for fast installation
|
For occasionally moved machine parts
|
For occasionally moved machine parts
|
Cable designation
|
2YY (ST) CY 2x2x0,64/1,5-100 GN
|
2YH (ST) C99Y 2x2x0,64/1,5-100 GN
|
2YY (ST) CY 2x2x0,75/1,5-100 LI GN
|
2YH (ST) C99Y 2x2x0,75/1,5-100 LI GN
|
Cable length
|
-
|
-
|
-
|
-
|
Electrical data
|
|
|
|
|
Damping ratio per length
|
|
|
|
|
|
52 dB/km
|
0.065 dB/m
|
60 dB/km
|
0.065 dB/m
|
|
195 dB/km
|
0.22 dB/m
|
210 dB/km
|
0.22 dB/m
|
Impedance for frequency range 1 MHz … 100 MHz
|
100 Ω
|
100 Ω
|
100 Ω
|
100 Ω
|
Relative symmetrical tolerance of the surge impedance at 1 MHz … 100 MHz
|
15 %
|
15 %
|
15 %
|
15 %
|
Near-end crosstalk per length at 1 MHz ... 100 MHz
|
500 dB/km
|
0.5 dB/m
|
500 dB/km
|
0.5 dB/m
|
Transfer impedance per length at 10 MHz
|
10 mΩ/m
|
10 mΩ/m
|
20 mΩ/m
|
20 mΩ/m
|
Loop resistance per length
|
115 Ω/km
|
115 Ω/km
|
120 Ω/km
|
120 Ω/km
|
Insulation resistance coefficient
|
-
|
-
|
-
|
-
|
Operating voltage RMS value
|
100 V
|
100 V
|
100 V
|
100 V
|
percentage NVP value
|
66 %
|
66 %
|
66 %
|
66 %
|
Mechanical data
|
|
|
|
|
Number of electrical wires
|
4
|
4
|
4
|
4
|
Design of shield
|
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
|
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
|
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
|
Overlapped aluminum-clad foil, sheathed in a braided screen of tin-plated copper wires
|
Design of the electrical connection FastConnect
|
Yes
|
Yes
|
Yes
|
Yes
|
AWG number
|
-
|
-
|
-
|
-
|
Core diameter of the AWG22 core
|
0.64 mm
|
0.64 mm
|
0.75 mm
|
0.75 mm
|
Outer diameter
|
|
|
|
|
|
0.64 mm
|
0.64 mm
|
0.75 mm
|
0.75 mm
|
|
1.5 mm
|
1.5 mm
|
1.5 mm
|
1.5 mm
|
-
of the inner sheath of the cable
|
3.9 mm
|
3.9 mm
|
3.9 mm
|
3.9 mm
|
|
6.5 mm
|
6.5 mm
|
6.5 mm
|
6.5 mm
|
Symmetrical tolerance of outer diameter of cable sheath
|
0.2 mm
|
0.2 mm
|
0.2 mm
|
0.2 mm
|
Material
|
|
|
|
|
|
PE
|
PE
|
PE
|
PE
|
-
of the inner sheath of the cable
|
PVC
|
FRNC
|
PVC
|
FRNC
|
|
PVC
|
TPE (FR-TPE)
|
PVC
|
TPE (FR-TPE)
|
|
-
|
-
|
-
|
-
|
Color
|
|
|
|
|
-
of the insulation of data wires
|
white / yellow / blue / orange
|
white / yellow / blue / orange
|
white / yellow / blue / orange
|
white / yellow / blue / orange
|
|
green
|
green
|
green
|
green
|
Bending radius
|
|
|
|
|
|
19.5 mm
|
26 mm
|
32.5 mm
|
32.5 mm
|
|
49 mm
|
52 mm
|
52 mm
|
52 mm
|
|
-
|
-
|
-
|
-
|
Number of bending cycles
|
-
|
-
|
-
|
-
|
|
-
|
-
|
-
|
-
|
Number of torsion cycles with torsion by ± 180° on 1 m cable length
|
-
|
-
|
-
|
-
|
Traction stress maximum
|
150 N
|
150 N
|
150 N
|
150 N
|
Weight per length
|
67 kg/km
|
59 kg/km
|
68 kg/km
|
68 kg/km
|
Permitted ambient conditions
|
|
|
|
|
Ambient temperature
|
|
|
|
|
|
-40 … +75 °C
|
-40 … +75 °C
|
-25 … +75 °C
|
-40 … +75 °C
|
|
-40 … +75 °C
|
-40 … +75 °C
|
-25 … +75 °C
|
-40 … +75 °C
|
|
-40 … +75 °C
|
-40 … +75 °C
|
-25 … +75 °C
|
-40 … +75 °C
|
|
-20 … +60 °C
|
-20 … +60 °C
|
-10 … +60 °C
|
-20 … +60 °C
|
Ambient condition for (standard) operation mode
|
-
|
-
|
-
|
-
|
Protection class IP
|
-
|
-
|
-
|
-
|
Burning behaviour
|
flame resistant according to UL 1685 (CSA FT4)
|
flame resistant according to IEC 60332-1-2
|
flame resistant according to UL 1685 (CSA FT4)
|
flame resistant according to IEC 60332-1-2
|
Chemical resistance
|
|
|
|
|
|
oil resistant according to IEC 60811-2-1 (4 h / 70°C)
|
oil resistant according to DIN EN 50290-2-22 (VDE 0819), (7x24h/90°C), UL13 Sec.40 (96h/100°C)
|
Conditional resistance
|
oil resistant according to DIN EN 50290-2-22 (VDE 0819), (7x24h/90°C), UL13 Sec.40 (96h/100°C)
|
|
Conditional resistance
|
Conditional resistance
|
Conditional resistance
|
Conditional resistance
|
|
Conditional resistance
|
Conditional resistance
|
Conditional resistance
|
Conditional resistance
|
Radiological resistance to UV radiation
|
Resistant
|
Resistant
|
Resistant
|
Resistant
|
Product properties, functions, components general
|
|
|
|
|
Product feature
|
|
|
|
|
|
No
|
No
|
No
|
No
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Cable length with 100BaseTX for Industrial Ethernet
|
100 m
|
100 m
|
85 m
|
85 m
|
Standards, specifications, approvals
|
|
|
|
|
UL/ETL listing with 300 V rating
|
Yes: cULus / CMG / PLTC/ ITC(UL) / Sun Res
|
Yes: c(ETL)us, CM, PLTC, SUN RES
|
Yes: c(UL)us, CMG / PLTC / Sun Res / OIL RES
|
Yes: c(ETL)us, CM, PLTC, SUN RES
|
UL/ETL style with 600 V rating
|
yes
|
No
|
No
|
No
|
Verification of suitability
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
Yes
|
|
-
|
-
|
-
|
-
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Standard for structured cabling
|
Cat5e
|
Cat5e
|
Cat5e
|
Cat5e
|
Marine classification association
|
|
|
|
|
-
American Bureau of Shipping Europe Ltd. (ABS)
|
No
|
No
|
No
|
No
|
|
No
|
No
|
No
|
No
|
|
No
|
No
|
No
|
No
|
|
No
|
No
|
No
|
No
|
-
Lloyds Register of Shipping (LRS)
|
No
|
No
|
No
|
No
|